Logo

Introducing Our New Products UV Lamp, Self Contain Freezer Unit and Heat Pump

AD Bar
   
        Commercial/Industrial Unit
 
Home
Air Conditional
Refrigeration
Heat Pump
SCAR-XB-Serial
SCAR-HB-Serial
SCAR-GB-Serial
SCAM-XB-Serial
SCAW-RB-Serial
Ventilation
Electrical
UV Lamp
UV Ballast
Solar Equipment
Oxygen concentrator
Contacts
 
 
 
 
Commercial and Industrial Heatpump Unit - Heatpump Unit
 
Features/Benefits
-

-

-

-
-

-


-

-

-
-
-
Base Frame and external panel made of polyeste
powder coated steel.
Extremely compact structurae, easy demountable for
access
High efficiency compressor with R410A refrigerant
Reverse cycle valve
Intelligent controller and adjustment by quickmind
microprocessor with possibility or remote control
Carful protection functions such as high pressure, low
pressure, overheating, overload, antifreezing, phase
order, discharge temp., etc.
Water side equiped with efficient tube in tube heat
exchanger.
Air heat exchanger (Fin Coil) with hyrophilic coating
or copper fin
Automatic defrosting function include
Thermostatic expansion valve
General testing an operational test carried out for every
unit before package in factory.
   
Capacity Range From: 1 - 27 Tons For More Detail: Download
MODEL: SCAR-__-XB 5 8 12 16 20
Rated heating capacity BTUH 16,481 24,226 37,534 51,182 64,831
Tons 1 2 3 4 5
Watt 4,830 7,100 11,000 15,000 19,000
Hot water supply T/h 0 0 0 0 0
Heating input  power Watt 1,150 1,700 2,340 3,400 4,100
Rated heating input current  Amp. 5 7 10 15 18
COP 4.2 4.18 4.6 4.4 4.63
Output water temperature Deg. C 60 Deg. C
Power Supply V/P/Hz 220V / 1P / 50-60Hz 220-415-440V / 1-3P / 50-60Hz
Noise level dB(A)  48 50 53 53 55
Weight KGS. 75 85 120 150 155
Working temperature range Deg. C ﹣20 Deg. C ~ 43 Deg. C
Water temp control precise Deg. C ± 1 Deg. C
Throttle type Electronic expansion valves/thermostatic expansion valves
Refrigerant Type R410A, R407C, R22
Compressor Type Rotary Hermetically sealed scroll
Quantity 1 1 1 1 1
Safety functions Overheating protection, phase protection, under-voltage protection, delay-start protection
Air source heatexchanger
Type Finned heat exchanger
Quantity 1 1 1 1 1
Fan type Axial big twist Angle fan
Motor power Watt 40 50 100 200 300
Hot water side heat exchanger Type High efficient spiral tube in tube heat exchanger
Water flow m3/H 0.84 1.22 1.86 2.44 3.27
Water pressure kPa 20 20 27 29 30
pipe size DN 20 20 20 25 25
Max. working pressure kPa 1,000 1,000 1,000 1,000 1,000
Advised water tank m3 0.15-0.5 0.25-0.7 1.2-1.8 1.5-2.5 2.5-3.5
 
MODEL: SCAR-__-XB 24 28 40 60 80 100
Rated heating capacity BTUH 78,479 92,469 129,661 194,833 259,323 324,153
Tons 7 8 11 16 22 27
Watt 23,000 27,100 38,000 57,100 76,000 95,000
Hot water supply T/h 0 1 1 1 2 2
Heating input  power Watt 4,680 5,900 8,200 12,200 16,200 20,500
Rated heating input current  Amp. 10 11 13 20 27 33
COP 4.7 4.59 4.64 4.68 4.69 4.63
Max running current Amp. 14.5 16 24 36 48 52
Output water temperature Deg. C 60 Deg. C
Power Supply V/P/Hz 415-440V / 3P / 50-60Hz
Noise level dB(A)  55 60 63 66 68 68
Weight KGS. 175 225 280 440 520 580
Working temperature range Deg. C ﹣20 Deg. C ~ 43 Deg. C
Water temp control precise Deg. C ± 1 Deg. C
Throttle type Electronic expansion valves/thermostatic expansion valves
Refrigerant Type R410A, R407C, R22
Compressor Type Hermetically sealed scroll
Quantity 1 1 2 3 4 4
Safety functions Overheating protection, phase protection, under-voltage protection, delay-start protection
Air source heat
exchanger Type Finned heat exchanger
Quantity 1 1 2 2 2 2
Fan type Axial big twist Angle fan
Motor power Watt 370 370 600 1,200 1,500 1,500
Hot water side heat exchanger Type High efficient spiral tube in tube heat exchanger
Water flow m3/H 3.72 4.66 6.53 9.81 13.07 16.3
Water pressure kPa 32 34 36 42 46 48
pipe size DN 25 25 32 40 50 50
Max. working pressure kPa 1,000 1,000 1,000 1,000 1,000 1,000
Advised water tank m3 2.5-4 3.5-5 5-7 8-10 12-14 15-20
NOTES:
-
-

-

-
Standard heating conditions:
Air side dry bulb temperature is 20Deg. C. wet bulb temperature is 15Deg. C. initial water temperature 15Deg. C.
output water temperature 55Deg. C
Manufacturer tested noise level showed above, are in laboratory. The noise level of installed unit could be different
with above data due to the surrounding conditions.
Manufacturer have the right to change the technical data due to technical improvement
     
   
Hit Counter   Copyright ©1994-2013  